Tegangan AC Nominal (50/60Hz) | 60 V | 120 V | 230 V | 230 V | 230 V | 400 V | ||
Tegangan Operasi Kontinu Maksimum (AC) (LN) | Uc | 75 V | 150 V | 275V | 320 V | 385 V | 440 V | |
(N-PE) | Uc | 255V | ||||||
Arus Debit Nominal (8/20 μs) (LN) / (N-PE) | In | 10kV / 10kA | ||||||
Arus Pelepasan Maksimum (8/20 μs) (LN) / (N-PE) | Imaks | 20 kA / 20 kA | ||||||
Tingkat Proteksi Tegangan (LN) / (N-PE) | Up | 0,2kV/1,5kV | 0,6kV/1,5kV | 1,3kV/1,5kV | 1.5kV/1.5kV | 1.5kV/1.5kV | 1.8kV/1.5kV | |
Ikuti Peringkat Interupsi Saat Ini (N-PE) | Ifi | 100LENGAN | ||||||
Waktu merespon | (LN) / (N-PE) | tA | < 25 ns / < 100 ns | |||||
Sekering Cadangan (maks) | 125 A gL/gG | |||||||
Rating Arus Hubungan Pendek (AC) (LN) | lSCCR | 10 kA | ||||||
TOV Menahan 5 detik | (LN) | UT | 90V | 180V | 335V | 335V | 335V | 580V |
TOV 120 mnt | (LN) | UT | 115V | 230V | 440V | 440V | 440V | 765V |
mode | Menahan | Menahan | Gagal Aman | Gagal Aman | Gagal Aman | Gagal Aman | ||
TOV Menahan 200ms | (N-PE) | UT | 1200V | |||||
Mekanik & Lingkungan | ||||||||
Rentang Suhu Operasi | Ta | -40ºF hingga +158ºF [-40ºC hingga +70ºC] | ||||||
Kelembaban Pengoperasian yang Diijinkan | RH | 5%...95% | ||||||
Tekanan atmosfer dan ketinggian | 80k Pa ... 106k Pa / -500 m.....2000 m | |||||||
Torsi Sekrup Terminal | Mmaks | 39,9 lbf ·dalam [4,5 Nm] | ||||||
Potongan Melintang Konduktor (maks) | 2 AWG (Padat, Terdampar) / 4 AWG (Fleksibel) | |||||||
35 mm2 (Padat, Terdampar) / 25 mm2 (Fleksibel) | ||||||||
Pemasangan | Rel DIN 35 mm, EN 60715 | |||||||
Tingkat Perlindungan | IP 20 (bawaan) | |||||||
Bahan Perumahan | ||||||||
Termoplastik: Gelar Pemadam UL 94 V-0 |
Fokus pada penyediaan solusi mong pu selama 5 tahun.